![]() | - Complete measuring bridge for transformers - Resistance, ratio, dual and heat loss measurements - Automatic phase selection with no reclamping - Automatic vector group detection - Built in components MRC 7100, PAW 7100, BED 7100 - robust case with keyboard drawer and warning light | ||||
![]() | - Resistance and ratio measurements - For transformers up to 1200 MVA - Automatic measuring without manual comparison - Additionally displays phase angle and magentizing current - tap changer control for measuring all taps automatically - Heat up measurement including algorhythm (resistance at t=0) - Automatic vector group detection (with PAW 7100) - Dual measuring method (with PAW 7100) - more info .... | ||||
![]() | - Phase selector for the MRC 7100 - Full connection to the transformer - Automatic phase switching and tap changing - No further reclamping necessary - Enables vector group detection - more info .... | ||||
![]() | - Control panel for the MRC 7100 / PAW 7100 - Special keys for inputting vector group - Special keys for inputting phase(s) - Keys for h. v., l. v. as well as dual - Keys for ratio, resistance and dual measurements - Key for starting automatic vector group detection - more info .... | ||||
![]() | - max. 1000 kV possible with transducers - max. 1000 kA possible with transducers - 550 V (chained) 6 A directly connectable - Measures and displays: Voltages, currents, - powers, short connection results, frequency - freely selectable voltage and current dividers - more info .... | ||||
![]() | - Resistance measuring bridge for transformers - Measuring capacity 500 uOhm - 1000 Ohm - Up to 100 MVA (internal current), 500 MVA (external) - maximum resolution 0,1 uOhm - Heat up measurement with algorhythm (resistance at t=0) - Measuring error +/- 0,1 % of MV, +/- 1 digit - Temperature measuring and compensation to 20° Celsius - more info .... | ||||
![]() | - Resistance measuring bridge for transformers - Measuring capacity 50 uOhm - 22 kOhm - up to 500 MVA and more - measuring current 10 mA - 30 A selectable - maximum resolution 0.01 uOhm - Heat up measurement with algorhythm (resistance at t=0) - Measuring error +/- 0.05% of MV, +/- 0.05% FS - Temperature measuring and compensation to 20° Celsius - more info .... | ||||
![]() | - mobile ratio transformer measuring bridge - measureable ratios 0.900 - 15,000 - Measuring voltages 8-40-120-180-230 V - Displays ratio, phase angle, magentizing current - and set point deviation - Measuring error +/- 0.1 % of MV, +/- 2 digit - Easy input of vector group and phase(s) - more info .... | ||||