MR 5-10 BAT
- Special instrument for low resistances.
- Measuring ranges 500,0 uOhm - 500,0 Ohm
- Max. resolution 0.1 uOhm, 4-pol measurement due to Kelvin
- Measuring current 10 mA to 10 A selectable

- Useful for cables, transformers, fuses, bus bars, switchgears etc.
- Universal use due to thermovoltage comp., PT100
- Contact error detection and interference voltage suppression
- Dataport: RS232C, battery powered incl. internal loading device
- more info ....
MR 5-40
- Special instrument for low resistance and high inductive objects
- Measuring range from 50 µOhm to 1,000 Ohm
- Resolution 0.1 µOhm (4-pole-connection due Kelvin)
- Current up to 4A or 40 A selectable

- special for measurement of transformers, motors, cables ...
- short measuring time due to fast loading voltage and high current
- special error diagnostic und noise surpression
- data-transfer via RS232C, temperature calculation by PT100
- more info ....
MRG 5 - digital teraohm meter
- Digital high resistance teraohmmeter
- Measuring ranges 100 kOhm - 1 TOhm
- Max. resolution 100 TOhm

- Measuring voltage 100 V - 1,500/3,000/5,000 V selectable (typ dependend)
- Measuring time 5 s - 600 s selectable
- LC display with backlight
- Ports: RS232C
- more info ....
MRG 5-TR - digital teraohm meter
- Digital high resistance teraohmmeter
- Measuring ranges 100 kOhm - 1 TOhm
- Max. resolution 100 TOhm

- Measuring voltage 100 V - 1,500/3,000/5,000 V selectable (typ dependend)
- Measuring time 5 s - 600 s selectable
- LC display with backlight
- Ports: RS232C
- more info ....
PWR 1 - mobile ratio measuring bridge
- mobile ratio transformer measuring bridge
- measureable ratios 0.8 - 1,500
- Measuring voltages 5 V (CT) 50 V (PT/VT)

- Displays ratio, phase angle, magentizing current
- and exitation voltage
- Measuring error +/- 0,2 % of MV, +/- 2 digit
- Power source by line or battery
- more info ....
PWR 1-3 - mobile ratio measuring bridge
- 3-phase mobile ratio transformer measuring bridge
- measureable ratios 0.8 - 1,500
- Measuring voltages 5 V (CT) 50 V (PT/VT)

- Displays ratio, phase angle, magentizing current
- and exitation voltage
- Measuring error +/- 0,2 % of MV, +/- 2 digit
- Power source by line or battery
- more info ....